hil_set_analog_input_ranges hil_set_clock_frequency navigation bar

hil_set_analog_output_ranges

Sets the ranges of the analog outputs.

Description

The hil_set_analog_output_ranges function sets the ranges of the analog outputs. Not all cards support programmable output ranges. Some cards only allow the ranges of all outputs to be set to the same value, rather than allowing each analog output to have a separate output range. Refer to the documentation for your card for details on the features supported by the card.

The units for the minimum and maximum values are typically Volts, but may be Amps or a unit appropriate to the specific card.

Prototype

t_error
hil_set_analog_output_ranges(t_card card, const t_uint32 analog_channels[], t_uint32 num_channels,
                             const t_double minimums[], const t_double maximums[]);
    

Parameters

t_card card

A handle to the board, as returned by hil_open.

const t_uint32 * analog_channels

An array containing the numbers of the analog output channels whose ranges will be configured. Channel numbers are zero-based. Thus, channel 0 is the first channel, channel 1 the second channel, etc.

Select a board type from the list for board-specific details: .

t_uint32 num_channels

The number of channels specified in the analog_channels, minimums and maximums arrays.

const t_double * minimums

An array of doubles (t_double) containing the minimum value of the output range for the corresponding channel in the analog_channels array. This array must be the same size as the analog_channels array.

const t_double * maximums

An array of doubles (t_double) containing the maximum value of the output range for the corresponding channel in the analog_channels array. This array must be the same size as the analog_channels array.

Return value

The return value is 0 if the analog output ranges are configured successfully. Otherwise a negative error code is returned. Error codes are defined in quanser_errors.h. A suitable error message may be retrieved using msg_get_error_message.

Error codes

QERR_HIL_SET_ANALOG_INPUT_RANGES_NOT_SUPPORTED

This function is not supported by the board-specific HIL driver for this board type.

QERR_INVALID_CARD_HANDLE

An invalid card handle was passed as an argument. Once a card has been closed using hil_close the card handle is invalid.

QERR_TOO_MANY_ANALOG_OUTPUT_CHANNELS

Too many analog output channels were specified.

QERR_INVALID_ANALOG_OUTPUT_CHANNEL

One of the analog output channels that was specified is not a valid channel number. Channel numbers range from 0 to one less than the number of channels.

QERR_MISSING_ANALOG_OUTPUTS

The array of analog output channels is NULL even though the number of analog outputs specified is non-zero.

QERR_MISSING_ANALOG_MINIMUMS

The array of minimum values is NULL even though the number of channels specified is non-zero.

QERR_MISSING_ANALOG_MAXIMUMS

The array of maximum values is NULL even though the number of channels specified is non-zero.

Requirements

Include Files

Libraries

hil.h

hil.lib;quanser_runtime.lib;quanser_common.lib

Examples

/*
* Set the range of analog output #0 to ±10V, the range of analog output #3 to 0..5V
* and the range of output #5 to ±5V.
*/
t_uint32 channels[] = {  0,  3,  5 };
t_double minimums[] = { -10, 0, -5 };
t_double maximums[] = { +10, 5, +5 };
t_error  result = hil_set_analog_output_ranges(card, channels, ARRAY_LENGTH(channels), minimums, maximums);
    

See Also

 